FAQ
FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-F Series
FAQ
Keyword Search
FAQ within [ MELSEC-F Series ]
-
Connecting local stations to the FX3U-16CCL-M
No, local stations cannot be connected to the FX3U-16CCL-M. Remote I/O stations, remote device stations, and intelligent device stations can be connected to... More Details >>
- No:24791
- Release Date:2019/02/28 09:06
- Category: MELSEC-F Series , Network/Communication
-
Use of latched (battery backed) type auxiliary relay
If the OUT instruction using a latched (battery backed) type auxiliary relay number exists in a sequence program, the information held may be overwritten by ... More Details >>
- No:24877
- Release Date:2019/04/15 08:07
- Category: MELSEC-F Series , Main Unit
-
The thickness of wireshould be2 square millimeters or more, andclass D grounding (grounding resistance: 100 Ω or less) should be performed. More Details >>
- No:24899
- Release Date:2019/04/15 11:30
- Category: MELSEC-F Series , Main Unit
-
One FX3U-ENET-ADP can be connected at the last stage (left end) of adapters for the FX3U series. *The FX3U-ENET-ADP is a communication special adapter and o... More Details >>
- No:24912
- Release Date:2019/04/17 11:39
- Category: MELSEC-F Series , Main Unit
-
Adding two channels of the RS-232C port in the FX3G series
Select the 40-point or 60-point type FX3G series main unit. In this case, two FX3G-232-BDs can be connected. When FX3G-CNV-ADP is used, anFX3U-232ADP can be ... More Details >>
- No:24926
- Release Date:2019/04/17 11:42
- Category: MELSEC-F Series , Main Unit
-
Gratis warranty term of the FX programmable controllers
The longest gratis warranty term after manufacturing shall be eighteen (18) months. For details, refer to the gratis warranty term explained in the applicabl... More Details >>
- No:24928
- Release Date:2019/04/17 11:42
- Category: MELSEC-F Series , Main Unit
-
E-mail sending/receiving function of the FX3U-ENET-L
E-mail sending function is supported, but receiving function is not available. More Details >>
- No:24930
- Release Date:2019/04/17 11:39
- Category: MELSEC-F Series , Network/Communication
-
Extension blocks and units that can be used in the FX3U series
The operation is not guaranteed. Please select the extension blocks and units from FX2N series. More Details >>
- No:24935
- Release Date:2019/04/18 14:24
- Category: MELSEC-F Series , Main Unit , I/O Extension
-
It is not possible to extend the length of the extension cable to over 65cm. Place the main unit separately by using the parallel link or N:N Network functio... More Details >>
- No:24941
- Release Date:2019/04/18 14:25
- Category: MELSEC-F Series , Accessories
-
Output numbers of the FX programmable controllers
Since they are octal, the number after Y7 is Y10 and after Y77 is Y100. More Details >>
- No:24946
- Release Date:2019/04/18 14:26
- Category: MELSEC-F Series
31-40 of Total 198