Inverse time delay operating characte...
It is a characteristic that operating time inversely become shorter as current increases. For Molded Case Circuit Breakers, protection characteristic meeting... More Details >>
It is a method which breaks short circuit current with both upstream and downstream circuit breakers. For example, in the case that short circuit current at ... More Details >>
Type AC: Operates with AC Type A: Operates not only with AC but also with pulsating current <Reference> TYPE B: Operates with DC More Details >>
Calorific value of the circuit breaker
1. The internal resistance (per pole) is described in the catalog and technical notes. 2. Power consumption (W) = RI^2 x Poles = Resistance (Ω) x Load curre... More Details >>
lower limit of operational voltage fo...
It is DC 24V. More Details >>
ACB add earth leakage protection
When earth leakage current protection module (ER) is attached, it is possible to protect against earth leakage current. "Trip" or "Alarm signal output" can b... More Details >>
ACB combination Ground fault protecti...
It is not possible to combine them at the same time. You need to choose one of them. More Details >>
For Shunt Trip (SHT), it is the time from voltage application to open ACB main contact * AE3200-SW or less, AE4000-SWA: 0.04 sec or less* AE4000-SW to AE6300... More Details >>
It is the Earth Leakage Circuit Breaker with rated residual operating current of 30mA or less. More Details >>