Start main contents

Factory Automation

FAQ

Factory Automation

FAQAbout Products

  • Font Size
  • S
  • M
  • L

FAQ within [ Air Circuit Breakers ]

1-10 of Total 24

prev 1 / 3page next
  • ACB Ground fault protection

    Ground fault protection (GFR) is prepared as option, it is possible to detect and protect against ground fault current. "Trip" or "Alarm signal output" can b... More Details >>

    • No:22412
    • Release Date:2018/08/31 14:33
  • ACB OCR alarm

    It is a standard equipment (automatic reset type) and 30ms of one-pulse is output at overload tripping. Hold-type circuit is necessary since the output time ... More Details >>

    • No:22428
    • Release Date:2018/08/31 14:33
  • ACB test position

    The test position is a position where a main circuit is in the "disconnected" state and only control circuit is in the "connected" state. Control circuit che... More Details >>

    • No:22405
    • Release Date:2018/08/31 14:33
  • ACB How to use MCR

    It is special relay characteristic for selective co-ordination. When closing ACB (changing from OFF to ON), the instantaneous tripping characteristic is effe... More Details >>

    • No:22402
    • Release Date:2018/08/31 14:33
  • ACB trip indication

    Generally, there is no Mechanical Trip indication of continuous output for AE-SW. It is necessary to indicate electrically by using OCR Alarm (AL) output or ... More Details >>

    • No:22432
    • Release Date:2018/08/31 14:33
  • ACB closing time

    The time between application of voltage to the closing coil (CC) and closing of the main contact is 0.08 sec or less. More Details >>

    • No:22440
    • Release Date:2018/08/31 14:33
  • ACB opening time

    For Shunt Trip (SHT), it is the time from voltage application to open ACB main contact * AE3200-SW or less, AE4000-SWA: 0.04 sec or less* AE4000-SW to AE6300... More Details >>

    • No:22418
    • Release Date:2018/08/31 14:33
  • ACB drawout position

    Drawout type circuit breaker can be drawn-out and insert to the cradle without taking out the connecting conductor. As ACB is drawn out, it will be "connect ... More Details >>

    • No:22431
    • Release Date:2018/08/31 14:33
  • ACB General use Generator protection use

    General protection relay (WS) of AE-SW type Air Circuit Breaker has tripping characteristic and function for general use. However, we also provide the replay... More Details >>

    • No:22414
    • Release Date:2018/08/31 14:33
  • ACB How to store drawout handle

    Set the handle holder to the right side of the drawout frame with the included screw and nut, and store the drawout handle. However, the circuit breaker with... More Details >>

    • No:22437
    • Release Date:2018/08/31 14:33

1-10 of Total 24

Inquiries