Turning off the LCD display and backlight (ME96SS series).
It is impossible to turn off the LCD. It is possible to turn off back lights. When any button is not pressed for 5 minutes, the automatic off mode setting... More Details >>
- No:22171
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:42
-
Branch connection for MODBUS RTU communication
No, it is impossible. But Multi-drop connection is possible. For details, refer to connection examples as below. More Details >>
- No:24808
- Release Date:2019/03/27 14:44
-
The operating/storage temperature and humidity
Storage temperature range: -25 °C to +75 °C Operating temperature range: -5 °C to +55 °C (Average: 35 °C or lower) Operating humidity range: 0% to 85% an... More Details >>
- No:22153
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:56
-
Communication failure with the upper system through MODBUS RTU.
Please check the following items. (A) Is the power supplied between MA and MB? (When the power is not supplied, the display does not work.) (B) Is the wir... More Details >>
- No:22182
- Release Date:2018/08/27 16:41
- Update:2020/04/10 17:08
-
Recommended update period (ME96SS series).
The expected lifetime is 10 years. Is recommended to replace the device every 10 year. However the environment of installed location, such as temperature ... More Details >>
- No:22154
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:02
-
Availability for battery exchange for Logging Unit (ME96SS series).
The battery of the Logging unit (ME-0000BU-SS96) is NOT exchangeable. Please order a new unit. More Details >>
- No:22152
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:54
-
Compatibility between present model and new model for the CC-Link (ME96SS series).
The CC-Link is compatible with the new model. More Details >>
- No:22151
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:51
-
Accuracy class index of active energy
Accuracy class index of active energy is a number which gives the limits of the permissible percentage error as defined in the IEC62053-22. More Details >>
- No:37704
- Release Date:2020/01/29 18:36
-
Wire length for analog output and contact output(ME96SS series)
It depends on the service conditions. Refer to the following guidelines. ① Contact output Contact output for ME96 series is no-voltage "a" contact. The... More Details >>
- No:24807
- Release Date:2019/03/27 12:12
-
LCD COM is flashing (ME96SS series).
A reason varies with the connection situation of options. (Please refer to the section 6 of the User’s Manual.) In case of MODBUS RTU Error content: ... More Details >>
- No:22186
- Release Date:2018/08/27 16:41
- Update:2020/04/13 09:20