FAQ
FAQAbout Products
- FAQ > Energy Saving Supporting Devices > Energy Saving Supporting Devices > Energy Measuring Units
FAQ
Keyword Search
FAQ within [ Energy Measuring Units ]
-
Setting of "Master / slave setting switch" (Model: EMU4-D65).
It is assumed that setting of "Master/Slave setting switch" at the bottom of the Display Unit (Model: EMU4-D65) for the Energy Measuring Unit is wrong. Perfo... More Details >>
- No:22126
- Release Date:2018/08/27 16:41
-
Branch connection for MODBUS RTU communication
No, it is impossible. But Multi-drop connection is possible. For details, refer to connection examples as below. More Details >>
- No:24808
- Release Date:2019/03/27 14:44
-
How to measure circuits over 600A (EcoMonitorPlus / Light)
As shown in the figure below, a current transformer (CT) with a secondary current of 5A is attached to the measurement location, and a split-type current sen... More Details >>
- No:38042
- Release Date:2021/02/25 17:54
-
As to changing location of the decimal point and units of the measured value.
Since location of the decimal point or units of the measured value displayed is decided by Total load power, it is impossible to change location of the decim... More Details >>
- No:22139
- Release Date:2018/08/27 16:41
-
EcoWebServerIII's rated voltage value setting with VT connections
For 3P4W circuits, set the VT primary voltage value (between L and N). Except for 3P4W circuits, set the VT primary voltage value (between L and L). <Re... More Details >>
- No:38040
- Release Date:2021/02/25 17:54
-
As to indication of the measurement value of the electric energy (EcoMonitorPlus/Light).
It measures from 0kWh(MWh) after going round. Integer 4 digits : 9999.98→9999.99→0000.00→0000.01kWh(MWh) Integer 5 digits : 99999.8→99999.9→00000.0→0000... More Details >>
- No:22131
- Release Date:2018/08/27 16:41
-
Pulse magnification setting of EMU4-PX4(Pulse Input Unit)
Match the setting values with EMU4-PX4 and EcoWebServerIII. No need to consider one-cycle operation because it is automatically calculated in EcoWebServerII... More Details >>
- No:38041
- Release Date:2021/02/25 17:54
-
As to compensation for power failure of Logging Unit for the Energy Measuring Unit.
Since the setting value is stored into nonvolatile memory, it will not be lost. The clock, logging data and system log data are retained as long as a batter... More Details >>
- No:22138
- Release Date:2018/08/27 16:41
- Update:2018/09/07 13:07
-
As to Zero-Phase Current Transformer (ZCT) usable for the EcoMonitorPlus (Model: EMU4-LG1-MB).
Refer to the below table as to Zero-Phase Current Transformer usable for EcoMonitorPlus (Model: EMU4-LG1-MB). Note that the one made by another company is... More Details >>
- No:22129
- Release Date:2018/08/27 16:41
- Update:2018/08/31 14:17
-
Extension of cable of the Display Unit (Model: EMU4-D65).
It is possible to extend using an extension cable (Model: EMU2-CB-T1M, EMU2-CB-T5M, EMU2-CB-T10M). Secure the total length of the extension cable is less t... More Details >>
- No:22122
- Release Date:2018/08/27 16:41
1-10 of Total 36