    Pr.30 = "1" and Pr.70 = "0". More Details >>

    • No:21143
    • Release Date:2018/08/22 16:26
  • Brake resistor

    Use two resistors for the high-duty brake resistor FR-ABR-15K. (Connect two resistors of 18 ? in parallel.) More Details >>

    • No:21329
    • Release Date:2018/08/22 16:27
  • Terminals P1 and P

    Removal of the jumper between the terminals P1 and P is not necessary unless you are using the DC reactor.Set Pr.30 = "0" when using the brake unit.Since set... More Details >>

    • No:21921
    • Release Date:2018/08/22 16:30
  • Input phase loss

    Check if the input side voltage is equally applied to all three phases. The S phase voltage may be low because the input current flows when the voltage of th... More Details >>

    • No:21340
    • Release Date:2018/08/22 16:27
  • Frequency setting

    Yes, you can set Pr.20 to 20 Hz. More Details >>

    • No:21683
    • Release Date:2018/08/22 16:28
  • FR-Configurator

    The FR Configurator FR-SW3-SETUP-WJ can only allow for test operation.Since this is a tool to support the system launch and maintenance, it is not designed f... More Details >>

    • No:21914
    • Release Date:2018/08/22 16:30
  • Motor: SF-HJCA

    Configure the same setting as the SF-HRCA. Configure the same setting as the SF-HRCA. A700, E700, D700, F700PJ: Pr.71 = 50F700P, F700: Pr.71 = 1 (Reference) ... More Details >>

    • No:21136
    • Release Date:2018/08/22 16:26
  • Operation mode, PU operation mode switching

    Change Pr.340 (Communication startup mode selection) from "1" to "0".Power OFF and then ON the inverter.Operate the inverter according to the value of Pr.79 ... More Details >>

    • No:21870
    • Release Date:2018/08/22 16:29
  • PU operation

    If Pr.79 = 3, PU and EXT turn ON. Switching between PU and EXT is not available. Turn the setting dial to set the frequency and press the SET key to accept it. More Details >>

    • No:21695
    • Release Date:2018/08/22 16:28
  • Error "E.UVT" (undervoltage protection)

    The possible causes of the error UVT are as follows.- Low power supply voltage - Insufficient power supply capacity - Damage or failure Check the power suppl... More Details >>

    • No:21295
    • Release Date:2018/08/22 16:26