About Low-voltage Power Distribution Products

Do you provide a surge suppressors for a control coil which isapplicable for S-T65 to N800 type?
Category : 

Answer

There is no surge suppressor for a control coil. The control coil of S-T65 toS-N800 type has the AC operation DC excitation method and includes thesurge suppresing function. Therefore, a surge suppressor is not needed.