Indication values of the main body is different from an obtained value through MODBUS RTU/ TCP (ME96SS series).
The value of the power factor of each phase to be monitored through MODBUS does not match the indication values of the main body.
- Category :
-
Answer
Please check the register addresses.
The register address for the present value of the power factor of each phase is “0789”.
There are the register addresses receiving a maximum and a minimum value.
- Product Name
- Electronic Multi-Measuring Instrument
- Series
- ME96SS series