Print
The power factor does not match the indication values through MODBUS.
The value of the power factor of each phase to be monitored through MODBUS does not match the indication values of the main body.
Category :
FAQ
>
Low-voltage Power Distribution Products
>
Power Management Meters
>
Electrical Indicators
Answer
Please check the register addresses.
The register address for the present value of the power factor of each phase is “0789”.
There are the register addresses receiving a maximum and a minimum value.
Product Name
Electronic Multi-Measuring Instrument
Series
ME96SS series