FAQ
FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC
FAQ
Keyword Search
Programmable Controllers MELSEC
FAQ within [ Programmable Controllers MELSEC ]
-
Resolution provided for L60AD4
The maximum resolution for the user range setting does not change. More Details >>
- No:22827
- Release Date:2018/09/03 17:30
- Update:2018/09/22 15:24
- Category: MELSEC-L Series
-
- Ambient temperature: 25+/-5degrees Celsius with tolerance of +/-0.1% - Ambient temperature: 0 to 55degrees Celsius with tolerance of +/-0.3% (accuracy f... More Details >>
- No:22825
- Release Date:2018/09/03 17:30
- Update:2018/09/27 11:38
- Category: MELSEC-L Series
-
Sampling cycle of L60TCTT4(BW) and L60TCRT4(BW)
It is selectable from the following. - 500 ms/4 channels (Default)- 250 ms/4 channels More Details >>
- No:22824
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
- Ambient temperature: 25+/-5degrees Celsius Full scalex (+/-0.3%) - Ambient temperature: 0 to 55degrees Celsius Full scalex (+/-0.7%) More Details >>
- No:22823
- Release Date:2018/09/03 17:30
- Update:2018/09/27 11:35
- Category: MELSEC-L Series
-
Battery install position in LCPU
Open the cover at the bottom of the CPU module and install the battery. More Details >>
- No:22821
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Simultaneous use of auto logging and backup functions
The auto logging function and backup function cannot be used simultaneously. The backup function must be used after the logging function is stopped. (A singl... More Details >>
- No:22819
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
I/O assignment for additional modules connected to LCPU
In L02CPU(-P), the start I/O number of the additional module begins from 10H. In L26CPU-(P)BT, the number begins from 30H. More Details >>
- No:22808
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Number of data sampling points in LCPU logging function
Up to 1280 points. (128 points per setting, and up to 10 data logging settings) More Details >>
- No:22805
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
The minimum input response times are different. The minimum input response time is 100 microseconds for standard inputs, and 10 microseconds for high-speed i... More Details >>
- No:22804
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
-
Use of commercial SD memory cards
Yes. A commercial SD memory card can be used. (32 GB max.)Connectable SD memory cards that passed our operation check are listed in the technical bulletin. More Details >>
- No:22801
- Release Date:2018/09/03 17:30
- Category: MELSEC-L Series
771-780 of Total 976