FAQ
FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-L Series
FAQ
Keyword Search
FAQ within [ MELSEC-L Series ]
-
I/O assignment for additional modules connected to LCPU
In L02CPU(-P), the start I/O number of the additional module begins from 10H. In L26CPU-(P)BT, the number begins from 30H. More Details >>
- No:22808
- Release Date:2018/09/03 17:30
-
Simultaneous use of auto logging and backup functions
The auto logging function and backup function cannot be used simultaneously. The backup function must be used after the logging function is stopped. (A singl... More Details >>
- No:22819
- Release Date:2018/09/03 17:30
-
Battery install position in LCPU
Open the cover at the bottom of the CPU module and install the battery. More Details >>
- No:22821
- Release Date:2018/09/03 17:30
-
- Ambient temperature: 25+/-5degrees Celsius Full scalex (+/-0.3%) - Ambient temperature: 0 to 55degrees Celsius Full scalex (+/-0.7%) More Details >>
- No:22823
- Release Date:2018/09/03 17:30
- Update:2018/09/27 11:35
-
Sampling cycle of L60TCTT4(BW) and L60TCRT4(BW)
It is selectable from the following. - 500 ms/4 channels (Default)- 250 ms/4 channels More Details >>
- No:22824
- Release Date:2018/09/03 17:30
-
- Ambient temperature: 25+/-5degrees Celsius with tolerance of +/-0.1% - Ambient temperature: 0 to 55degrees Celsius with tolerance of +/-0.3% (accuracy f... More Details >>
- No:22825
- Release Date:2018/09/03 17:30
- Update:2018/09/27 11:38
-
Resolution provided for L60AD4
The maximum resolution for the user range setting does not change. More Details >>
- No:22827
- Release Date:2018/09/03 17:30
- Update:2018/09/22 15:24
-
Availability of step ladders for FX in L series
Step ladders are not available in LCPU. There is no alternative function. More Details >>
- No:22752
- Release Date:2018/09/03 17:29
-
Remedy to an error message when performing online change in LCPU
After data is written to the program cache memory (SRAM), it is automatically transferred to the program memory (flash ROM). Therefore, additional online cha... More Details >>
- No:22763
- Release Date:2018/09/03 17:30
- Update:2018/09/22 10:50
-
No. It is necessary to configure one port to use the MELSOFT connection. More Details >>
- No:22765
- Release Date:2018/09/03 17:30
41-50 of Total 105