FAQ
FAQAbout Products
- FAQ > Controllers > Programmable Controllers MELSEC > MELSEC-L Series
FAQ
Keyword Search
FAQ within [ MELSEC-L Series ]
-
Number of points used for I/O assignment of LCPU built-in I/O function
X00 to X0F and Y00 to Y07 are sorted for each function. For more details, refer to "MELSEC-L CPU Module User's Manual (Built-In I/O Function)". More Details >>
- No:22762
- Release Date:2018/09/03 17:30
-
The conversion speed is 20 microseconds per channel. More Details >>
- No:22826
- Release Date:2018/09/03 17:30
-
Yes. As a guide, the processing time is shown below.For the logging condition, refer to figure 1 below. - For 16 devices: 2 ms - For 64 devices: 6 ms More Details >>
- No:22829
- Release Date:2018/09/03 17:30
- Update:2018/09/22 15:33
-
Usage of UPS (uninterruptible power supply)
No, it cannot be used. More Details >>
- No:22831
- Release Date:2018/09/03 17:30
-
Use SP.FWRITE instruction to save the data to an SD memory card in CSV format. More Details >>
- No:22727
- Release Date:2018/09/03 17:29
-
Boot operation from the standard ROM
The boot operation from the standard ROM is not possible. The program memory of LCPU is a flash ROM. Thus, writing in the program memory achieves a ROM opera... More Details >>
- No:22728
- Release Date:2018/09/03 17:29
-
The contents of the standard RAM and latch devices are not erased if the battery replacement is completed within three minutes, which is the backup power tim... More Details >>
- No:22733
- Release Date:2018/09/03 17:29
-
How to use L series extension modules
The extension module is used to configure the extension block when 10 modules or more are mounted to LCPU. Connect the branch module and the extension module... More Details >>
- No:22738
- Release Date:2018/09/03 17:29
-
Communication between CPUs via built-in Ethernet port in LCPU
The following communication methods are available between the built-in Ethernet ports in the L series CPUs.- Simple PLC communication function- Socket commun... More Details >>
- No:22746
- Release Date:2018/09/03 17:29
-
Update timing of LD75 current feed value and machine feed value
The values are updated at the timing described below. - Current feed value: 0.9 ms - Machine feed value: 0.9 ms More Details >>
- No:22748
- Release Date:2018/09/03 17:29
61-70 of Total 105