Limitation on the number of MELSOFT products that can be connected with the QJ71E71
In the TCP/IP connection, you can connect up to 17 MELSOFT products at the same time using a dedicated connection for system and the connections for users 1 ... More Details >>
- No:23063
- Release Date:2018/09/03 17:31
-
SB/SW refresh device setting with CC-Link
There are no problems even though the SB/SW refresh device has not been set. More Details >>
- No:23080
- Release Date:2018/09/03 17:31
-
You can set the parameters of the FL-net interface module with the data operation of the intelligent function module. For details and operation procedure of... More Details >>
- No:23084
- Release Date:2018/09/03 17:31
- Update:2018/09/26 13:19
-
Number of remote registers assigned to a remote I/O station
For "Remote Net(Ver.2 Mode)", the number of remote I/O's remote registers (RWw, RWr) is "0 Point". More Details >>
- No:22973
- Release Date:2018/09/03 17:31
-
"[ ]" in the CC-Link remote I/O modules' model name "AJ65[ ]BT" represents as follows: - None: Standard type - S: Compact type - F: Low profile waterpro... More Details >>
- No:22974
- Release Date:2018/09/03 17:31
- Update:2018/09/25 17:12
-
Clearing data in the QJ71C24N's receiving area buffer memory
Receiving data overwrites the buffer memory data. Writing 0 with a program can be performed but is unnecessary as the data is overwritten. More Details >>
- No:23009
- Release Date:2018/09/03 17:31
-
For CPU modules with 8192 I/O device points (X/Y0 to 1FFF), X/Y1000 and greater can be set as refresh devices. More Details >>
- No:23014
- Release Date:2018/09/03 17:31
-
Setting required to skip CC-Link slave station numbers
A CC-Link slave station number can be skipped by assigning the skipped number to a reserved station. A reserved station is counted as one of all the connecte... More Details >>
- No:23029
- Release Date:2018/09/03 17:31
-
Station number settings for MELSECNET/H networks
A station number can be skipped by setting the station as a reserved station. More Details >>
- No:23045
- Release Date:2018/09/03 17:31
-
Connecting terminating resistors for CC-Link communication
Connect terminating resistors to both ends of physical cables.A master station is not necessarily required to be connected to either end of its network. More Details >>
- No:23046
- Release Date:2018/09/03 17:31