Operation under torque limit in the speed control mode
Under a 50% torque limit, if the commanded speed (50 Hz in your example) cannot be achieved without torque exceeding 50%, since the torque does not exceed th... More Details >>
- No:21483
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-V200
-
Parameter No.79 (Operation mode)
You cannot cancel multi-speed command input. When the multi-speed command is input from the terminal, you cannot use the potentiometer. Use the inverter so t... More Details >>
- No:21467
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E500
-
The following causes are probable for persistent Err. display: 1. The terminals RES and SD are always short-circuited. 2. Operation panel contact or operatio... More Details >>
- No:21412
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E500
-
Output side earth (ground) fault overcurrent protection
1. How much is the sensitivity current? When the sum of the three-phase output current of the inverter reaches approximately 70% of the inverter rated curren... More Details >>
- No:21394
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-A024 , FREQROL-E500
-
If the output current is close to 25% of the rated current, output phase loss may occur when one or two phases of three phases go below 25%.Therefore, when a... More Details >>
- No:22052
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500
-
When Pr.79 is set to "3", the JOG operation is not available by turning ON the terminal JOG.Instead of the JOG function, you can set the low-speed RL of the ... More Details >>
- No:21760
- Release Date:2018/08/22 16:29
- Category: Inverters-FREQROL , FREQROL-E700 , FREQROL-D700 , FREQROL-A700 , FREQROL-F700 , FREQROL-F700P , FREQROL-F700PJ
-
Synchronous operation of two motors
When synchronously operating two motors, you need to detect speed from both motors. Each inverter is controlled based on this speed detection signal. As an e... More Details >>
- No:21540
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , Options , FREQROL-A024
-
It is considered to be caused by inverter PWM control. It can be suppressed by raising the PWM carrier frequency (Pr.72), but the entire noise and leakage cu... More Details >>
- No:21428
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-E500
-
Both parameter files (pr4) and system files (frc2) can be read. More Details >>
- No:20909
- Release Date:2018/08/22 16:25
- Category: Inverters-FREQROL , Engineering Software
-
Coasting operation of the inverter
To use an inverter using the external contact coast to stop (to shut off the inverter's output), short-circuit the terminals MRS and SD.For CC-Link operation... More Details >>
- No:22003
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500