Operation at the reversed phase connection (ME96SS series).
This model operates normally even at the reversed phase sequence. It is unnecessary to change wiring. More Details >>
- No:22170
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:41
- Category: Electrical Indicators
-
Display upon upper/lower limit alarm (ME96SS series).
The measurement elements, including the digital indication, the unit indication and the phase indication, flash. And the “ALARM” indication and the “HI” in... More Details >>
- No:22169
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:36
- Category: Electrical Indicators
-
Tolerance for overload (ME96SS series).
It is no influence on operating and characteristics even in the following cases. 1. Overcurrent 20 times of rated current is applied for 0.5 second. 2. Ov... More Details >>
- No:22159
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
About Low-voltage Power Distribution Products
US-N* type is controlled by DC power supply (12 to 24 VDC). However,UA-DR1/UA-SH1 driving-unit of option unit make it possible to control byAC power supply (... More Details >>
- No:23359
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
It is the number that can be opened/closed per hour under the conditions specified in the standard. More Details >>
- No:22436
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
"b contact" is normally closed contact, and It is also called "NC (Normally Closed) contact". More Details >>
- No:22435
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
High inst MCCB for transformer primary side
It is a circuit breaker which has higher instantaneous tripping current value in order to prevent unwanted tripping by magnetizing inrush current of a transf... More Details >>
- No:22358
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Use in Particular Applications
-
Standards for this model (ME96SS series).
This model is compliant with CE marking, UL standard, KC Mark and FCC/IC. More Details >>
- No:22146
- Release Date:2018/08/27 16:41
- Update:2020/04/10 14:27
- Category: Electrical Indicators
-
About Low-voltage Power Distribution Products
The permissible variation range of frequency (short time variation) is ±5%. More Details >>
- No:23371
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
Time rating is 60sec and the rest time is for 2 hours. More Details >>