FAQ
FAQAbout Products
- FAQ > Low-voltage Power Distribution Products > Contactors and Motor Starters
FAQ
Keyword Search
Contactors and Motor Starters
FAQ within [ Contactors and Motor Starters ]
-
About Low-voltage Power Distribution Products
The rated impulse withstand voltage of US-H* type is 6KV. This meets therequired impulse characteristic for power distribution equipment specifiedin IEC stan... More Details >>
- No:23329
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
We can not produce it. More Details >>
- No:23332
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is instantaneous capacity (Making VA) immediately after a control coil isenergized. In the case of DC operation, it is less than constant input. More Details >>
- No:23334
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is possible to install them by rotating 90℃ to the right or left from theregular installation except S-N600 and S-N800. It is not possible to rotate180℃ f... More Details >>
- No:23335
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
We can provide "CAN terminal" products for only US-N20?50(TE) type asspecial product.Type name:US-N20?50(TE)CX More Details >>
- No:23337
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The Earth Leakaga Circuit Breaker does not work since leakage current ofSSC is the current flowing from the main circuit element to the load sidewhen opening. More Details >>
- No:23338
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
Main circuit of US-H* type is used for only AC power supply. For DC powersupply, we provide US-KD8 type solid state contactor. More Details >>
- No:23339
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is time from magnetizing or demagnetizing a control coil to operatingcontact (turning contact "ON" or "OFF"). More Details >>
- No:23343
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The withstand voltage of US-H type is 2.5kV. The applied location is asbelow.1. Between a main circuit terminal and a control circuit terminal2. Between all ... More Details >>
- No:23344
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is the utilization category for opening/closing a motor load ofsemiconductor contactor specified in IEC60947-4-2. Utilization categoryAC-53a applies for "... More Details >>
- No:23345
- Release Date:2018/09/12 15:12
- Category: Motor Starters
41-50 of Total 142