FAQ


FAQAbout Products
- FAQ > Low-voltage Power Distribution Products > Low-voltage Circuit Breakers > Molded Case Circuit Breakers
FAQ
Keyword Search
FAQ within [ Molded Case Circuit Breakers ]
-
Almost MCCBs can be connected n reverse. Check the item column of specification table "reverse connection" in the catalog. If it says "Possible", MCCB can be... More Details >>
- No:22442
- Release Date:2018/08/31 14:33
-
It is possible to modify to Rear-connection type by Mitsubishi's certified staff. More Details >>
- No:22399
- Release Date:2018/08/31 14:33
-
It is overcurrent tripping characteristic zone which exceeds the rated current and does not exceed short time tripping zone (If without short time tripping ,... More Details >>
- No:22384
- Release Date:2018/08/31 14:33
-
Default setting of electronic breakers
Each setting knob of the overcurrent trip characteristic is set to the maximum value and then shipped if not specified. However, only the pre-alarm is set to... More Details >>
- No:22438
- Release Date:2018/08/31 14:33
-
Plug-in type NF1600-SEW produced
It is impossible. More Details >>
- No:24817
- Release Date:2019/04/09 15:16
-
It is the maximum voltage which meets the performance criteria for the rated operational voltage. More Details >>
- No:22367
- Release Date:2018/08/31 14:33
-
It means that it does not interfere with tripping operation even if a handle is held at "ON" position. (It trips when an overcurrent flows even if a handle i... More Details >>
- No:22378
- Release Date:2018/08/31 14:33
-
Storage temperature range of MCCBs and ELCBs
It is from -25 to 55℃ in Trip or OFF position. However, it shall be in an environment without condensation and freezing even in a short time. More Details >>
- No:22426
- Release Date:2018/08/31 14:33
-
It is voltage which ensures withstand voltage and it is used as basis to determine insulation distance. More Details >>
- No:22362
- Release Date:2018/08/31 14:33
-
If switching of neutral pole is not needed, it is possible to use 3-pole MCCB for 3-phase 4- wire circuit. Generally, it is recommended to use 4-pole circuit... More Details >>
- No:22385
- Release Date:2018/08/31 14:33