- No:20806
- Release Date:2018/08/22 16:24
-
Proper use of AC reactor and DC reactor
1. ACL has the input power factor of approximately 90% and DCL has the input power factor of approximately 95%. Therefore, DCL has a higher input power facto... More Details >>
- No:21949
- Release Date:2018/08/22 16:30
-
If using an inverter with capacity of 75K or higher, or motor with capacity of 75 kW or higher, always select and install the inverter based on the capacity ... More Details >>
- No:21112
- Release Date:2018/08/22 16:25
-
No, it cannot. The standard operation panel (FR-DU08) can be connected to the face of the board by using the FR-ADP (operation panel connection connector) an... More Details >>
- No:20898
- Release Date:2018/08/22 16:24
-
1. The BU brake unit does not have the fault output.Multiple BU brake units can be connected in parallel.2. Power supply voltage 480 V- What resistance value... More Details >>
- No:21930
- Release Date:2018/08/22 16:30
-
Installation necessity of a DC reactor
A DC reactor connection is required under the following conditions. - Inverter capacity is 75K or higher - Motor capacity is 75 kW or higher. If any of the a... More Details >>
- No:21077
- Release Date:2018/08/22 16:25
-
Pr.30 = "1" and Pr.70 = "0". More Details >>
- No:21143
- Release Date:2018/08/22 16:26
-
It is possible when Pr.23 = 0 (Current limit at regenerative driving). More Details >>
- No:20826
- Release Date:2018/08/22 16:24
-
Input "0" to the bit not to be sent. More Details >>
- No:20970
- Release Date:2018/08/22 16:25
-
Power factor improving reactor
Your understanding about the AC and DC reactors is correct. For the harmonics suppression effect obtained by using both types of reactors, refer to the table... More Details >>
- No:21994
- Release Date:2018/08/22 16:30