Since Pr.125 (Terminal 2 frequency setting gain frequency) is initially set to 60 Hz, change it to 85 Hz. More Details >>
- No:21907
- Release Date:2018/08/22 16:30
-
Set Pr.550 (NET mode operation command source selection) to "2" (PU connector is the command source).When operating the inverter using the USB connector, set... More Details >>
- No:21904
- Release Date:2018/08/22 16:30
-
Set Pr.340 (Communication startup mode selection) to other than "0".Also, set Pr.79 (Operation mode) to "0", "2", or "6".Powering the inverter on automatical... More Details >>
- No:21903
- Release Date:2018/08/22 16:30
-
You can start/stop operation, set the frequency, read/write parameters, and monitor the inverter via CC-Link communication. More Details >>
- No:21901
- Release Date:2018/08/22 16:29
-
If you are using CC-Link just to monitor the inverter and using the analog signal and multi-speed setting to set the frequency, you need to input them extern... More Details >>
- No:21900
- Release Date:2018/08/22 16:29
-
Yes.You can issue operation (forward/reverse), frequency setting, parameter read/write, and operation monitor commands. More Details >>
- No:21899
- Release Date:2018/08/22 16:29
-
You can purchase the FR-A7NC E kit cover alone.Contact the distributor. More Details >>
- No:21898
- Release Date:2018/08/22 16:29
-
For the inverter, the option card FR-A7NC is necessary. More Details >>
- No:21897
- Release Date:2018/08/22 16:29
-
Did you purchase the FR-A7NC?If the front cover is supplied with the FR-A7NC E kit, it will fit. More Details >>
- No:21895
- Release Date:2018/08/22 16:29
-
You can install only one option card.If you want to use two types of cards, replace the inverter with the FR-A700 series.If you can use RS485 communication i... More Details >>