FAQ within [ FREQROL-D700 ]

91-100 of Total 260

prev 10 / 26page next
  • Terminal FM

    You can connect a 1 mA full scale ammeter with internal resistance 300 Ω or lower. More Details >>

    • No:21680
    • Release Date:2018/08/22 16:28
  • Parameter

    Press the "MODE" key on the operation panel several times to display "P.0" and parameter setting screen. Then turn the setting dial to display "C..." screen ... More Details >>

    • No:21336
    • Release Date:2018/08/22 16:27
  • Frequency setting

    No. Use a frequency setting potentiometer with the resistance of 1 kΩ and B characteristics.Input voltage is not linear due to the inverter's internal impeda... More Details >>

    • No:21911
    • Release Date:2018/08/22 16:30
  • FR-PA02 built-in potentiometer

    Change Pr.146 (Built-in potentiometer switching) to "0" (built-in frequency setting potentiometer). More Details >>

    • No:21862
    • Release Date:2018/08/22 16:29
  • Cooling fan

    Pr.244 (Cooling fan operation selection) controls turning ON/OFF of the cooling fan and is initially set to "1". When the inverter is powered ON, the cooling... More Details >>

    • No:21670
    • Release Date:2018/08/22 16:28
  • Operation panel (DU04)

    The FR-DU04 can be used in the 700 series inverters, however, some restrictions apply and parameter copy is disabled. More Details >>

    • No:21261
    • Release Date:2018/08/22 16:26
  • Terminal FM

    No. This is because the current cannot flow if the total internal impedance of the meter connected to the terminal FM is 300 Ω or higher.You can connect mult... More Details >>

    • No:21864
    • Release Date:2018/08/22 16:29
  • Frequency setting

    Set Pr.13 (Starting frequency) or Pr.2 (Lower limit) to "5 Hz".Also set Pr.10 (DC injection brake operation frequency) to "5 Hz".The inverter does not operat... More Details >>

    • No:21790
    • Release Date:2018/08/22 16:29
  • External operation

    The inverter has the calibration function.Use Pr.125 (Terminal 2 frequency setting gain frequency) and Pr.C4 (Terminal 2 frequency setting gain) for calibrat... More Details >>

    • No:21849
    • Release Date:2018/08/22 16:29
  • Automatic restart after instantaneous power failure setting

    You also need to set Pr.57 (Restart coasting time).The function does not work just by setting Pr.162 unless setting this parameter.(For A700, F700, and F700P... More Details >>

    • No:21731
    • Release Date:2018/08/22 16:29

91-100 of Total 260