If you try to change a parameter in other than the PU operation mode, the mode specification error "Er4" may occur.Set the parameters in the PU operation mod... More Details >>
- No:21778
- Release Date:2018/08/22 16:29
-
It is not stored in a parameter but memorized as the frequency setting value after acceleration by the acceleration signal.You can also choose whether or not... More Details >>
- No:21733
- Release Date:2018/08/22 16:29
-
Operations cannot be enabled separately. You only can disable or enable all the operations. More Details >>
- No:21366
- Release Date:2018/08/22 16:27
-
For the Instruction Manual "Applied", fill in the request sheet which is included in the last part of the Instruction Manual "Basic", and fax it to the speci... More Details >>
- No:21341
- Release Date:2018/08/22 16:27
-
Select the inverter capacity so that the rated output current of inverter ? rated motor current × 1.1. More Details >>
- No:21326
- Release Date:2018/08/22 16:27
-
The detection time 1 s cannot be changed. More Details >>
- No:21277
- Release Date:2018/08/22 16:26
-
After setting Pr.79 (Operation mode selection) to "2" and Pr.340 (Communication startup mode selection) to "10", reset the inverter (or power ON again) to st... More Details >>
- No:21256
- Release Date:2018/08/22 16:26
-
No, it cannot. More Details >>
- No:21253
- Release Date:2018/08/22 16:26
-
Switching between PU and NET operation modes
Set Pr.340 (Communication startup mode selection) to "10".The operation mode can be switched between PU and NET by assigning X65 (PU-NET operation switching)... More Details >>
- No:21878
- Release Date:2018/08/22 16:29
-
The full scale of the frequency is initially set to 60 Hz and the frequency indication becomes the full scale at 60 Hz operation.To change the indication val... More Details >>
- No:21866
- Release Date:2018/08/22 16:29