Set Pr.37 (Speed display) to the speed obtained when operating the machine at the frequency set with Pr.505 (Speed setting reference). (For FR-F700/E700/D700... More Details >>
- No:21716
- Release Date:2018/08/22 16:29
-
Yes, you can use the setup software (FR-SW3-SETUP-WJ) to set it. More Details >>
- No:21711
- Release Date:2018/08/22 16:29
-
Set Pr.338 to "0" (NET) and Pr.339 to "1" or "2". More Details >>
- No:21674
- Release Date:2018/08/22 16:28
-
You can change the full-scale value by changing Pr.55 (Frequency monitor reference). The initial setting is 60 Hz. More Details >>
- No:21672
- Release Date:2018/08/22 16:28
-
Normally, Pr.80 and Pr.81 are the parameters that can be changed when the operation is stopped in the PU operation mode. The "Er4" is a mode designation erro... More Details >>
- No:21335
- Release Date:2018/08/22 16:27
-
Fault output terminal A, B, and C
Set the rated motor current to Pr.9. It is the heat protection setting for the motor, and thus the inverter does not shutoff immediately at the specified cur... More Details >>
- No:21324
- Release Date:2018/08/22 16:27
-
Connection cable of FR-Configurator
It is the standardized Mini-B connector. More Details >>
- No:21312
- Release Date:2018/08/22 16:26
-
Check that the wiring of the terminal 4 and 5 are not reversed. More Details >>
- No:21266
- Release Date:2018/08/22 16:26
-
After setting Pr.79 (Operation mode selection) to "2" and Pr.340 (Communication startup mode selection) to "10", reset the inverter (or power ON again) to st... More Details >>
- No:21256
- Release Date:2018/08/22 16:26
-
No, it cannot. More Details >>