  • CC-Link

    You cannot monitor the running frequency and conveyor speed (machine speed) simultaneously.The inverter does not have a function to output them simultaneously. More Details >>

    • No:21827
    • Release Date:2018/08/22 16:29
  • CC-Link

    You can check the fault records with Pr.544 (CC-Link extended setting) set to "12" for double setting.Set H74 for the instruction code and turn ON RYF. More Details >>

    • No:21829
    • Release Date:2018/08/22 16:29
  • CC-Link

    The FR-A7NC is designed for the FR-A700, FR-F700, and FR-F700P.The FR-A7NC E kit is designed for the FR-E700 with the dedicated cover. (Only the dedicated co... More Details >>

    • No:21830
    • Release Date:2018/08/22 16:29
  • CC-Link

    1. It depends on how Pr.338 (Communication operation command source) and Pr.339 (Communication speed command source) are set.2. The external terminal reset i... More Details >>

    • No:21838
    • Release Date:2018/08/22 16:29
  • CC-Link

    If Pr.340 (Communication startup mode selection) and Pr.79 (Operation mode selection) are set so that the inverter starts CC-Link operation from power-on and... More Details >>

    • No:21840
    • Release Date:2018/08/22 16:29
  • Frequency setting

    This is due to specifications that multi-speed selection is prioritized and setting with the setting dial is ignored.The setting dial is effective when multi... More Details >>

    • No:21843
    • Release Date:2018/08/22 16:29
  • Setting dial

    Yes. You can use the setting dial of the inverter to set the frequency as well as change the parameter values. More Details >>

    • No:21846
    • Release Date:2018/08/22 16:29
  • Frequency setting

    If Pr.79 (Operation mode) is set to "0" (PU/EXT switching mode), press the PU/EXT button on the operation panel to turn on the PU LED.Turn the setting dial t... More Details >>

    • No:21855
    • Release Date:2018/08/22 16:29
  • Parameter setting

    Change Pr.79 (Operation mode) to "3" (Combined operation mode) and short-circuit the external terminals STF and SD (or STR and SD for reverse rotation). More Details >>

    • No:21859
    • Release Date:2018/08/22 16:29
  • PU operation

    Set Pr.79 (Operation mode) to "1" (PU operation mode) and change Pr.161 (Frequency setting/key lock operation selection) to "1" (potentiometer mode).   More Details >>

    • No:21863