FAQ
FAQAbout Products
- FAQ > Drive Products > Inverters-FREQROL > FREQROL-A500
FAQ
Keyword Search
FREQROL-A500
FAQ within [ FREQROL-A500 ]
-
Torque characteristic at low speed
Torque is not guaranteed for slower than 0.5 Hz. Therefore, no data for this is published. Also, no torque is generated at 0 Hz. More Details >>
- No:21543
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
Faults history upon power failure
When an instantaneous power failure of 100 msec or longer occurs, the inverter is reset* and it is not recognized as a fault. Since it is not recognized as a... More Details >>
- No:21551
- Release Date:2018/08/22 16:28
- Category: Inverters-FREQROL , FREQROL-A500
-
To supply power via R1 and S1, 60 VA or higher is necessary for 22K or lower and 80 VA or higher is necessary for 30K to 55K.Note that the rush current of ap... More Details >>
- No:22043
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Pulse train output of terminal FM
Under Advanced magnetic flux vector control, the output frequency varies due to slip compensation. This may cause the output frequency monitor value to chang... More Details >>
- No:22054
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
Speed change due to power supply voltage fluctuation
1. The output frequency satisfies the "control specification/frequency precision" even when the power supply voltage changes, but the output voltage cannot r... More Details >>
- No:22069
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500 , FREQROL-E500
-
Inverter stop-on-contact control
Use the FREQROL-A500 series inverter with the optional FR-A5NC.Then, you can implement both of stop-on-contact control and CC-Link operation. More Details >>
- No:22089
- Release Date:2018/08/22 16:30
- Category: Inverters-FREQROL , FREQROL-A500
-
- The installation size is compatible for the following capacities. Compatible: 200 V class 90K or lower, 400 V class 7.5K or lower and 18.5K to 280K- The in... More Details >>
- No:21110
- Release Date:2018/08/22 16:25
- Category: FREQROL-A800 , FREQROL-A500
-
Inverter operation at instantaneous power failure
When performing the automatic restart after instantaneous power failure, input the operation signal (STF or STR) and selection of automatic restart after ins... More Details >>
- No:21371
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
When Advanced magnetic flux vector control (Pr.80, 81) is used, the machine speed constant is controlled. The inverter calculates the motor slip and compensa... More Details >>
- No:21374
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500
-
Using FR-A540 inverter on CC-Link
Answer to question 1 When the CC-Link option goes faulty, OPT (option error) occurs and the inverter's fault output is triggered. When communication is lost ... More Details >>
- No:21391
- Release Date:2018/08/22 16:27
- Category: Inverters-FREQROL , FREQROL-A500