  • Short-circuit detection

    Overload tolerance of an over current relay is 200 A, 1 second. Adjust CT ratio and others not to input more than 200 A. More Details >>

    • No:23711
    • Release Date:2018/09/19 17:16
  • Detection of current

    It operates on a root mean square value of a fundamental wave. More Details >>

    • No:23710
    • Release Date:2018/09/19 17:16
  • A lighting condition of RUN

    Because this relay derives the control power from input of the CT secondary current, when the input current falls below about 0.5 A for 2-phase input or abou... More Details >>