Overhead time before and after the startup of an interrupt program with a MELSEC iQ-R series CPU module
How long is the overhead time before and after the startup of an interrupt program with a MELSEC iQ-R series CPU module?
- Category :
Answer
Although it depends on interrupt factors, the overhead time before startup becomes 10.8 to 23.8 [us]
and the time after startup becomes 6.5 to 17.4 [us].