Refresh timing of bit data and word data in the same CC-Link station

Sometimes the refresh timing of bit data and word data do not match in the same CC-Link station What is the cause?
Category : 

Answer

Cyclic data is sometimes separated into new and old data by two words (32 bits) with auto refresh timing. Checking "Block data assurance per station" of the CC-Link parameter setting "Operation Setting" assures the integrity of the cyclic data RX, RY, RWr, and RWw.