Operation error of the instruction that handles the present value of a high-speed counter
Back
No : 24907
Release Date : 2019/04/15 11:32
Print
Operation error of the instruction that handles the present value of a high-speed counter
The applied instruction that handles the present value of the high-speed counter cannot be executed due to an operation error.
Category :
FAQ
>
Controllers
>
Programmable Controllers MELSEC
>
MELSEC-F Series
FAQ
>
Controllers
>
Programmable Controllers MELSEC
>
MELSEC-F Series
>
High-Speed Counting
Answer
The present value register of the high-speed counter is the 32-bit register. The applied instruction handling the 32-bit register must be the 32-bit instruction.
If the 16-bit instruction is used, an operation error occurs.