• No : 22173
  • Release Date : 2018/08/27 16:41
  • Update : 2020/04/10 16:46
  • Print

Measuring harmonics range (ME96SS series).

Which range of harmonics is measured?
Category : 

Answer

 ME96SSHB-MB
 • Total harmonics and odd orders of harmonics from 1st to 31st
 • Effective value and distortion rate.
 • Harmonic current and Harmonic voltage
 ME96SSRB-MB
 • Total harmonics and odd orders of harmonics from 1st to 19th.
 • Effective value and distortion rate.
 • Harmonic current and Harmonic voltage.
 ME96SSEB-MB
 • Total harmonics.
 • Effective value and distortion rate.
 • Harmonic current and Harmonic voltage.
 
 
Product Name
Electronic Multi-Measuring Instrument
Series
ME96SS series