It depends on the service conditions.
Refer to the following guidelines.
① Contact output
     Contact output for ME96 series is no-voltage "a" contact.
     The wire length shall be up to 2km.

② Analog output
     The resistance value connected to analog output of ME96SS series shall be 600Ω or less.