FAQ within [ Low-voltage Circuit Breakers ]
-
UVT is an internal accessory which trips a circuit breaker in the case that circuit voltage decreases from 70% to 35% or less, and turns it "ON" after resett... More Details >>
- No:22349
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
Setting change operation while power is on
It is forbidden to change the characteristic when the breaker ON. Over current trip and earth leakage trip characteristics should be changed by a person with... More Details >>
- No:37699
- Release Date:2020/01/18 09:58
- Category: Molded Case Circuit Breakers , Air Circuit Breakers
-
The test position is a position where a main circuit is in the "disconnected" state and only control circuit is in the "connected" state. Control circuit che... More Details >>
- No:22405
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
This contact(SBC) is used to auxiliary switch(AXb) contact. When Drawout type ACB is moved from "test" position to "disconnect" position, AXb contact will b... More Details >>
- No:22416
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
3P MCCB in 1-phase 2-wire circuit
It is possible. Refer to the figure for connection as below. More Details >>
- No:24811
- Release Date:2019/04/09 15:18
- Category: Molded Case Circuit Breakers
-
Horizontal connection type (standard: AE-SW up to 3200A except 2000-SWA), Vertical connection (VT) type (standard: 2000-SWA,4000-SWA -6300-SW) and Front conn... More Details >>
- No:22417
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
It is special relay characteristic for selective co-ordination. When closing ACB (changing from OFF to ON), the instantaneous tripping characteristic is effe... More Details >>
- No:22402
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Electronic MCCB 400-1600A How to change rated current and characteristic curve (Except CE breakers)
First, turn OFF the upstream circuit breaker and the relevant circuit breaker. You must not work in the state where voltage is applied to the relevant circui... More Details >>
- No:22439
- Release Date:2018/08/31 14:33
- Update:2018/08/31 14:35
- Category: Molded Case Circuit Breakers
-
Ground fault protection (GFR) is prepared as option, it is possible to detect and protect against ground fault current. "Trip" or "Alarm signal output" can b... More Details >>
- No:22412
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
A circuit breaker must have interrupting ratings. These are classified as rated short-circuit breaking capacities in IEC 60947-2.e rated ultimate short-circu... More Details >>
- No:22341
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers