ACB add earth leakage protection
When earth leakage current protection module (ER) is attached, it is possible to protect against earth leakage current. "Trip" or "Alarm signal output" can b... More Details >>
- No:22420
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
How to install cassette type accessories
A circuit breaker shall be Trip position when installing Cassette type accessory. The breaker may be damaged if installing in "ON" or "OFF" position. Moreove... More Details >>
- No:22422
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
No, you must not use 2-pole circuit breaker as 1-pole circuit breaker (series connection as only single phase ). If using it as 1-pole circuit breaker, these... More Details >>
- No:22382
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Use with 24V, 0.5A or more for AC and DC in normal use. If the breakers are used less than 24V, use with 6V, 1A or more. Moreover, regular inspection of is ... More Details >>
- No:22401
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
It may not trip a fault current or degrade insulation after tripping. When you connect the device in reverse, you must select a reverse-connectable model. More Details >>
- No:22345
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Horizontal allowable distance when installing ACB
Flatness of mounting plane: 1 mm or less.In addition, it is necessary to consider the horizontality of the panel. More Details >>
- No:37698
- Release Date:2020/01/17 17:32
- Category: Air Circuit Breakers
-
The circuit breaker is designed to attain a predetermined value of limiting non-actuating time corresponding to a given value of residual current. Our time-d... More Details >>
- No:22351
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
It is an earth leakage current (Effective value of residual operating current) which definitely trips Earth Leakage Circuit Breaker and Earth Leakage Relay ... More Details >>
- No:22353
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
It is possible to use it if you connect with right and left poles, not neutral pole. Since electronic circuit power supply for earth leakage detection is tak... More Details >>
- No:22359
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
It is the Earth Leakage Circuit Breaker with rated residual operating current of 30mA or less. More Details >>
- No:22390
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers