Max. operational voltage for AC/DC Co...
When it is connected as special connection, AC/DC compatible circuit breaker can be used with DC 250V or more (3-pole type is DC400V and 4-pole type is DC500... More Details >>
It is a button in order to trip MCCB. It is used for regular inspection of the switching mechanism, and trip condition of MCCB when Alarm switch (AL) and Shu... More Details >>
Default setting of electronic breakers
Each setting knob of the overcurrent trip characteristic is set to the maximum value and then shipped if not specified. However, only the pre-alarm is set to... More Details >>
Storage temperature range of MCCBs an...
It is from -25 to 55℃ in Trip or OFF position. However, it shall be in an environment without condensation and freezing even in a short time. More Details >>
How to install cassette type accessories
A circuit breaker shall be Trip position when installing Cassette type accessory. The breaker may be damaged if installing in "ON" or "OFF" position. Moreove... More Details >>
The applicable voltage is 440V or less. Moreover, High-speed type can be used from 85 to 484V, and Time-delay type can be used from 170 to 484V. More Details >>
This contact(SBC) is used to auxiliary switch(AXb) contact. When Drawout type ACB is moved from "test" position to "disconnect" position, AXb contact will b... More Details >>
"a contact" is normally opened contact, and It is also called "NO (Normally Opened) contact". More Details >>
The number of trip durability by using SHT and UVT is 10% of the opening/closing number including the number of trips by overcurrent, trip button and test bu... More Details >>
Insulating barrier in the package
Use the insulation barrier if they are packed with. If not using that, breaking performance is not guaranteed. For models that the insulation barrier is not ... More Details >>