FAQ within [ Low-voltage Circuit Breakers ]
-
ACB combination Ground fault protection and earth leakage protection
It is not possible to combine them at the same time. You need to choose one of them. More Details >>
- No:22419
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Change Electronic relay characteristics when it is energized
Only electricians who have enough technical knowledge should change the setting of overcurrent tripping and earth leakage tripping characteristics. Moreover,... More Details >>
- No:22409
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
The operating handle is an external accessory for a circuit breaker and there is no safety standard for the operating handle itself. Therefore, there is no C... More Details >>
- No:22408
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
EAL (Earth Leakage Alarm switch) is a switch that electrically displays tripping state of Earth Leakage Circuit Breaker by eartheleakage/ground fault. EAL do... More Details >>
- No:22404
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
When Power-Fuse (PF) is used as a high-voltage side protection device, coordination with MCCBs on the secondary side shall be achieved. Therefore, MCCB has l... More Details >>
- No:22403
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Use in Particular Applications
-
It is possible to modify to Rear-connection type by Mitsubishi's certified staff. More Details >>
- No:22399
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
It is the Earth Leakage Circuit Breaker with rated residual operating current of higher than 30mA but not exceeding 1000mA. We provide the products of "100, ... More Details >>
- No:22395
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
Transformers, wires and welded materials may be damaged if an abnormal energization occurs exceeding the energization cycles that are set for the inverter we... More Details >>
- No:22393
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Use in Particular Applications
-
Default setting from the factory
The knob of the sensitivity current selector is set to the maximum value when shipping in order to prevent unwanted earth leakage tripping when Earth Leakage... More Details >>
- No:22391
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
It is overcurrent tripping characteristic zone which exceeds the rated current and does not exceed short time tripping zone (If without short time tripping ,... More Details >>
- No:22384
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers