- FAQ > Low-voltage Power Distribution Products > Low-voltage Circuit Breakers
FAQ
Keyword Search
FAQ within [ Low-voltage Circuit Breakers ]
-
A circuit breaker must have interrupting ratings. These are classified as rated short-circuit breaking capacities in IEC 60947-2.e rated ultimate short-circu... More Details >>
- No:22341
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
AX (Auxiliary switch) is a switch which electrically displays the ON / OFF state. The markings are 14/AXa, 12/AXb and 11/AXc.* If the circuit breaker itself ... More Details >>
- No:22354
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
It is a method which breaks short circuit current with both upstream and downstream circuit breakers. For example, in the case that short circuit current at ... More Details >>
- No:22357
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
F-type and V-type operating handle
Both of F-type and V-type can remotely operate a circuit breaker in the panel board and the design of 800A fame or less are unified. Features are as follows.... More Details >>
- No:22389
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
ACB add earth leakage protection
When earth leakage current protection module (ER) is attached, it is possible to protect against earth leakage current. "Trip" or "Alarm signal output" can b... More Details >>
- No:22420
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Residual non-operating current
It is a current that does not leak-trip even if there is ground fault current or leakage current. In the standard, it is 50 % of the rated residual operating... More Details >>
- No:22356
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
If switching of neutral pole is not needed, it is possible to use 3-pole MCCB for 3-phase 4- wire circuit. Generally, it is recommended to use 4-pole circuit... More Details >>
- No:22385
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
For ACB, Line and Load are not defined on the main circuit terminals. Reverse connection is available without any limitation. More Details >>
- No:22425
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Almost ELCBs can be connected n reverse. Check the item column of specification table "reverse connection (below 230 V AC)" in the catalog. If it says "Possi... More Details >>
- No:22434
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
The range of ambient temperature is from -10 to 40 degree Celsius for not only MCCB but also including Earth Leakage Circuit breaker, Earth Leakage Relay and... More Details >>
- No:22352
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers