- FAQ > Low-voltage Power Distribution Products > Low-voltage Circuit Breakers
FAQ
Keyword Search
FAQ within [ Low-voltage Circuit Breakers ]
-
For Shunt Trip (SHT), it is the time from voltage application to open ACB main contact * AE3200-SW or less, AE4000-SWA: 0.04 sec or less* AE4000-SW to AE6300... More Details >>
- No:22418
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Earth leakage protective coordination
Since the total electric circuit length of upstream circuit breaker side is longer than that of downstream circuit breaker, constant earth leakage current b... More Details >>
- No:22369
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
Use with 24V, 0.5A or more for AC and DC in normal use. If the breakers are used less than 24V, use with 6V, 1A or more. Moreover, regular inspection of is ... More Details >>
- No:22401
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Ground fault protection (GFR) is prepared as option, it is possible to detect and protect against ground fault current. "Trip" or "Alarm signal output" can b... More Details >>
- No:22412
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
A shunt trip (SHT) is an internal accessory which electrically and remotely trips a circuit breaker. When the supply voltage of the SHT is remained between 7... More Details >>
- No:22342
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
Electronic MCCB 400-1600A How to change rated current and characteristic curve (Except CE breakers)
First, turn OFF the upstream circuit breaker and the relevant circuit breaker. You must not work in the state where voltage is applied to the relevant circui... More Details >>
- No:22439
- Release Date:2018/08/31 14:33
- Update:2018/08/31 14:35
- Category: Molded Case Circuit Breakers
-
Generally, there is no Mechanical Trip indication of continuous output for AE-SW. It is necessary to indicate electrically by using OCR Alarm (AL) output or ... More Details >>
- No:22432
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
It is a button in order to mechanically trip a circuit breaker outside. It is used to confirm switching mechanism at the regular maintenance or sequence-chec... More Details >>
- No:22368
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
The range of ambient temperature is from -10 to 40 degree Celsius for not only MCCB but also including Earth Leakage Circuit breaker, Earth Leakage Relay and... More Details >>
- No:22352
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Drawout type circuit breaker can be drawn-out and insert to the cradle without taking out the connecting conductor. As ACB is drawn out, it will be "connect ... More Details >>
- No:22431
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers