FAQ
![](/usr/file/attachment/q&a.jpg)
![](/usr/file/attachment/q&a_sp.jpg)
FAQAbout Products
![](/usr/file/attachment/img_mv-1_sm.jpg)
- FAQ > Low-voltage Power Distribution Products > Low-voltage Circuit Breakers
FAQ
Keyword Search
FAQ within [ Low-voltage Circuit Breakers ]
-
How to connect to 2-pole breaker
(1) When "N" is marked on the breaker,connect the N phase wire as marked. (2) When "N" is not marked on the breaker, N phase wire can be connected to eith... More Details >>
- No:37700
- Release Date:2020/01/17 08:58
- Category: Molded Case Circuit Breakers
-
Type name of the operating handle
F-2SV is standard, F-2SVE is for emergency use. The difference is the color of the handle and its surroundings parts. More Details >>
- No:38028
- Release Date:2021/01/22 17:37
- Category: Accessories and Related Components
-
MCCB stands for "Molded Case Circuit Breaker." This is defined in the IEC standard, IEC 60947-2 and in the UL standard, UL 489. MCB stands for "Miniature Ci... More Details >>
- No:22340
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
AL (Alarm switch) is a switch which electrically displays tripping state of a circuit breaker.The markings of the switch are 8/ALa, 96/ALb and 95/ALc.*When t... More Details >>
- No:22350
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
It means that it does not interfere with tripping operation even if a handle is held at "ON" position. (It trips when an overcurrent flows even if a handle i... More Details >>
- No:22378
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Short circuit current calculation software
You can calculate that with MELSHORT 2 (Free of charge). More Details >>
- No:22394
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Default setting of electronic breakers
Each setting knob of the overcurrent trip characteristic is set to the maximum value and then shipped if not specified. However, only the pre-alarm is set to... More Details >>
- No:22438
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
B-ST is possible. More Details >>
- No:24814
- Release Date:2019/04/09 15:17
- Category: Molded Case Circuit Breakers
-
4-pole type in 100VAC or 110VAC
The rated operational voltages for them are 200 to 440VAC. If using them in 100VAC or 110VAC circuit, earth-leakage protection does not operate. More Details >>
- No:24820
- Release Date:2019/04/09 15:10
- Category: Earth Leakage Circuit Breakers
-
It means a space between the edge of a exhaust port and panel component ( such as wall or duct) of a circuit breaker. The arc space is needed for smoothly di... More Details >>
- No:22373
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
11-20 of Total 124