It is a button in order to mechanically trip a circuit breaker outside. It is used to confirm switching mechanism at the regular maintenance or sequence-chec... More Details >>
- No:22368
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
The test position is a position where a main circuit is in the "disconnected" state and only control circuit is in the "connected" state. Control circuit che... More Details >>
- No:22405
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Horizontal allowable distance when installing ACB
Flatness of mounting plane: 1 mm or less.In addition, it is necessary to consider the horizontality of the panel. More Details >>
- No:37698
- Release Date:2020/01/17 17:32
- Category: Air Circuit Breakers
-
Ground fault protection (GFR) is prepared as option, it is possible to detect and protect against ground fault current. "Trip" or "Alarm signal output" can b... More Details >>
- No:22412
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Use with 24V, 0.5A or more for AC and DC in normal use. If the breakers are used less than 24V, use with 6V, 1A or more. Moreover, regular inspection of is ... More Details >>
- No:22401
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Operating ambient temperature is set to - 10℃ to 40℃. ( However, its average over a period of 24h does not exceed 35℃.) In the case that the ambient temperat... More Details >>
- No:22370
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
The time between application of voltage to the closing coil (CC) and closing of the main contact is 0.08 sec or less. More Details >>
- No:22440
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Drawout type circuit breaker can be drawn-out and insert to the cradle without taking out the connecting conductor. As ACB is drawn out, it will be "connect ... More Details >>
- No:22431
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
For Shunt Trip (SHT), it is the time from voltage application to open ACB main contact * AE3200-SW or less, AE4000-SWA: 0.04 sec or less* AE4000-SW to AE6300... More Details >>
- No:22418
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
It is an instantaneous tripping circuit breaker which does not have overcurrent tripping characteristic for standard circuit breaker and only protects agains... More Details >>
- No:22383
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Use in Particular Applications