It is possible to modify to Rear-connection type by Mitsubishi's certified staff. More Details >>
- No:22399
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
AL (Alarm switch) is a switch which electrically displays tripping state of a circuit breaker.The markings of the switch are 8/ALa, 96/ALb and 95/ALc.*When t... More Details >>
- No:22350
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
Shunt Trip for CP30-BA can be provided. However, the pole of that with Shunt Trip is "Relay type" without overcurrent tripping element. Internal circuit is "... More Details >>
- No:22423
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Equipment
-
It means that it does not interfere with tripping operation even if a handle is held at "ON" position. (It trips when an overcurrent flows even if a handle i... More Details >>
- No:22378
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
AL/AX/SHT/UVT terminal markings and wire colors
The color of terminal identification tube and lead wire is same.For one AL switch, 98/ALa terminal : red, 96/ALb terminal : blue, 95/ALc terminal : grayFor S... More Details >>
- No:22396
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
MCB can be used at 85% or less relative humidity and no condensation. More Details >>
- No:24822
- Release Date:2019/04/09 15:11
- Category: Miniature Circuit Breakers
-
How to select at Inverter circuit
Basically you have to consider the effect of harmonic waves, but there are two ways as below. 1. Refer to the recommended rated current by inverter manufactu... More Details >>
- No:22360
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
It is a protection method which only trips the related circuit breaker and other fault-free circuit does not trip and continues power supply in the event of... More Details >>
- No:22366
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
"a contact" is normally opened contact, and It is also called "NO (Normally Opened) contact". More Details >>
- No:22410
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
Storage temperature range of MCCBs and ELCBs
It is from -25 to 55℃ in Trip or OFF position. However, it shall be in an environment without condensation and freezing even in a short time. More Details >>