ELCB applicable to harmonics and surge
Compared with general circuit breakers, Earth Leakage Circuit Breaker applicable to harmonics and surge has earth leakage current detecting characteristic wh... More Details >>
AC Breakers used at DC circuit
It is not possible to use a circuit breaker for AC in DC circuit. Since the Arc-Extinguishing Device structure of circuit breaker for DC is different from th... More Details >>
Residual non-operating current
It is a current that does not leak-trip even if there is ground fault current or leakage current. In the standard, it is 50 % of the rated residual operating... More Details >>
Setting change operation while power ...
It is forbidden to change the characteristic when the breaker ON. Over current trip and earth leakage trip characteristics should be changed by a person with... More Details >>
(1) and (2) are impossible. More Details >>
The operating handle is an external accessory for a circuit breaker and there is no safety standard for the operating handle itself. Therefore, there is no C... More Details >>
Use with 24V, 0.5A or more for AC and DC in normal use. If the breakers are used less than 24V, use with 6V, 1A or more. Moreover, regular inspection of is ... More Details >>
This function is equipped in electronic circuit breaker. It outputs an alarm when pre-alarm current setting current (the rated current or less) is over and l... More Details >>
Select rated current sensitivity
Please select rated current sensitivity ,according to the protection purpose and the protective grounding resistance value of the load equipment. If you alre... More Details >>
3P MCCB in 1-phase 2-wire circuit
It is possible. Refer to the figure for connection as below. More Details >>