"a contact" is normally opened contact, and It is also called "NO (Normally Opened) contact". More Details >>
- No:22410
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
For ACB, Line and Load are not defined on the main circuit terminals. Reverse connection is available without any limitation. More Details >>
- No:22425
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
For Shunt Trip (SHT), it is the time from voltage application to open ACB main contact * AE3200-SW or less, AE4000-SWA: 0.04 sec or less* AE4000-SW to AE6300... More Details >>
- No:22418
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Ground fault protection (GFR) is prepared as option, it is possible to detect and protect against ground fault current. "Trip" or "Alarm signal output" can b... More Details >>
- No:22412
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Short circuit current calculation software
You can calculate that with MELSHORT 2 (Free of charge). More Details >>
- No:22394
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
It means a space between the edge of a exhaust port and panel component ( such as wall or duct) of a circuit breaker. The arc space is needed for smoothly di... More Details >>
- No:22373
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
ELCB applicable to harmonics and surge
Compared with general circuit breakers, Earth Leakage Circuit Breaker applicable to harmonics and surge has earth leakage current detecting characteristic wh... More Details >>
- No:22344
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
lower limit of operational voltage for DC
It is DC 24V. More Details >>
- No:24816
- Release Date:2019/04/09 15:17
- Category: Molded Case Circuit Breakers
-
The time between application of voltage to the closing coil (CC) and closing of the main contact is 0.08 sec or less. More Details >>
- No:22440
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
ACB combination Ground fault protection and earth leakage protection
It is not possible to combine them at the same time. You need to choose one of them. More Details >>
- No:22419
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers