Use with 24V, 0.5A or more for AC and DC in normal use. If the breakers are used less than 24V, use with 6V, 1A or more. Moreover, regular inspection of is ... More Details >>
When Power-Fuse (PF) is used as a high-voltage side protection device, coordination with MCCBs on the secondary side shall be achieved. Therefore, MCCB has l... More Details >>
Insulating barrier in the package
Use the insulation barrier if they are packed with. If not using that, breaking performance is not guaranteed. For models that the insulation barrier is not ... More Details >>
The number of trip durability by using SHT and UVT is 10% of the opening/closing number including the number of trips by overcurrent, trip button and test bu... More Details >>
Change Electronic relay characteristi...
Only electricians who have enough technical knowledge should change the setting of overcurrent tripping and earth leakage tripping characteristics. Moreover,... More Details >>
"a contact" is normally opened contact, and It is also called "NO (Normally Opened) contact". More Details >>
It is possible to reverse-connect if the circuit voltage of UL789 listed products is AC240V or less. Since they are double standard products of UL/CSA and CE... More Details >>
It is possible to produce micro-load AL and AX switch for MCCBs/ELCBs. However, if you need the products compatible with the standards (CE marking product an... More Details >>
ACB combination Ground fault protecti...
It is not possible to combine them at the same time. You need to choose one of them. More Details >>
The applicable voltage is 440V or less. Moreover, High-speed type can be used from 85 to 484V, and Time-delay type can be used from 170 to 484V. More Details >>