It is possible to reverse-connect if the circuit voltage of UL789 listed products is AC240V or less. Since they are double standard products of UL/CSA and CE... More Details >>
- No:22411
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
ACB combination Ground fault protection and earth leakage protection
It is not possible to combine them at the same time. You need to choose one of them. More Details >>
- No:22419
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
It means a space between the edge of a exhaust port and panel component ( such as wall or duct) of a circuit breaker. The arc space is needed for smoothly di... More Details >>
- No:22373
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
AL/AX direct connection to PLC
It is necessary to use AL and AX switches that are suitable for the specification of PLC input unit. Generally AL and AX switch for micro-load are used for i... More Details >>
- No:22398
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
When Power-Fuse (PF) is used as a high-voltage side protection device, coordination with MCCBs on the secondary side shall be achieved. Therefore, MCCB has l... More Details >>
- No:22403
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Use in Particular Applications
-
EAL (Earth Leakage Alarm switch) is a switch that electrically displays tripping state of Earth Leakage Circuit Breaker by eartheleakage/ground fault. EAL do... More Details >>
- No:22404
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
This contact(SBC) is used to auxiliary switch(AXb) contact. When Drawout type ACB is moved from "test" position to "disconnect" position, AXb contact will b... More Details >>
- No:22416
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
4-pole type in 100VAC or 110VAC
The rated operational voltages for them are 200 to 440VAC. If using them in 100VAC or 110VAC circuit, earth-leakage protection does not operate. More Details >>
- No:24820
- Release Date:2019/04/09 15:10
- Category: Earth Leakage Circuit Breakers
-
This function is equipped in electronic circuit breaker. It outputs an alarm when pre-alarm current setting current (the rated current or less) is over and l... More Details >>
- No:22377
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
The applicable voltage is 440V or less. Moreover, High-speed type can be used from 85 to 484V, and Time-delay type can be used from 170 to 484V. More Details >>
- No:22421
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers