FAQ within [ Low-voltage Circuit Breakers ]
-
ACB How to check the operating characteristic
Y-2005 type field test equipment (it is sold separately) enable to check the operating characteristic easily. The test is conducted by connecting the test te... More Details >>
- No:22429
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
ACB add earth leakage protection
When earth leakage current protection module (ER) is attached, it is possible to protect against earth leakage current. "Trip" or "Alarm signal output" can b... More Details >>
- No:22420
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
The number of trip durability by using SHT and UVT is 10% of the opening/closing number including the number of trips by overcurrent, trip button and test bu... More Details >>
- No:22407
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
Use with 24V, 0.5A or more for AC and DC in normal use. If the breakers are used less than 24V, use with 6V, 1A or more. Moreover, regular inspection of is ... More Details >>
- No:22401
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
The range of ambient temperature is from -10 to 40 degree Celsius for not only MCCB but also including Earth Leakage Circuit breaker, Earth Leakage Relay and... More Details >>
- No:22352
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
AL (Alarm switch) is a switch which electrically displays tripping state of a circuit breaker.The markings of the switch are 8/ALa, 96/ALb and 95/ALc.*When t... More Details >>
- No:22350
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
Shunt Trip for CP30-BA can be provided. However, the pole of that with Shunt Trip is "Relay type" without overcurrent tripping element. Internal circuit is "... More Details >>
- No:22423
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Equipment
-
F-type and V-type operating handle
Both of F-type and V-type can remotely operate a circuit breaker in the panel board and the design of 800A fame or less are unified. Features are as follows.... More Details >>
- No:22389
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
ELCB Default setting Time-delay type sensitivity
Both of the adjustment knob is set to the maximum value when shipping in order to prevent unwanted earth leakage tripping when Earth Leakage Circuit Breaker ... More Details >>
- No:22388
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
If switching of neutral pole is not needed, it is possible to use 3-pole MCCB for 3-phase 4- wire circuit. Generally, it is recommended to use 4-pole circuit... More Details >>
- No:22385
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
31-40 of Total 123