FAQ


FAQAbout Products
- FAQ > Low-voltage Power Distribution Products > Low-voltage Circuit Breakers
FAQ
Keyword Search
FAQ within [ Low-voltage Circuit Breakers ]
-
Default setting from the factory
The knob of the sensitivity current selector is set to the maximum value when shipping in order to prevent unwanted earth leakage tripping when Earth Leakage... More Details >>
- No:22391
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
Operating characteristics described in our catalog (if there is no "Note" particularly) mean operating time when it starts to carry current from the conditio... More Details >>
- No:22374
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
AX (Auxiliary switch) is a switch which electrically displays the ON / OFF state. The markings are 14/AXa, 12/AXb and 11/AXc.* If the circuit breaker itself ... More Details >>
- No:22354
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
For ACB, Line and Load are not defined on the main circuit terminals. Reverse connection is available without any limitation. More Details >>
- No:22425
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
If switching of neutral pole is not needed, it is possible to use 3-pole MCCB for 3-phase 4- wire circuit. Generally, it is recommended to use 4-pole circuit... More Details >>
- No:22385
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Earth Leakage Circuit Breaker and Earth Leakage Relay operate at higher than 50% but not exceeding 100% of the rated residual operating current IΔn. The eart... More Details >>
- No:22364
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
The time between application of voltage to the closing coil (CC) and closing of the main contact is 0.08 sec or less. More Details >>
- No:22440
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Inverse time delay operating characteristic
It is a characteristic that operating time inversely become shorter as current increases. For Molded Case Circuit Breakers, protection characteristic meeting... More Details >>
- No:22387
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
This function is equipped in electronic circuit breaker. It outputs an alarm when pre-alarm current setting current (the rated current or less) is over and l... More Details >>
- No:22377
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
ACB combination Ground fault protection and earth leakage protection
It is not possible to combine them at the same time. You need to choose one of them. More Details >>
- No:22419
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
31-40 of Total 123