It is not possible to use standard AE-SW in DC circuit. Special DC use AE-SW is provided if specified. More Details >>
- No:22446
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Rating of a circuit breaker for transformers primary protection
When making a transformer to energize, a large inrush current may flow. The circuit breaker is therefore required to prevent unwanted trip. The selection of ... More Details >>
- No:22343
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
It means that it does not interfere with tripping operation even if a handle is held at "ON" position. (It trips when an overcurrent flows even if a handle i... More Details >>
- No:22378
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
ACB combination Ground fault protection and earth leakage protection
It is not possible to combine them at the same time. You need to choose one of them. More Details >>
- No:22419
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Release element in neutral (4P breaker)
AE-SW 4-poles with WS relay (general protection) has overcurrent protection for neutral-pole. The tripping characteristic is same as phase-pole. Moreover, A... More Details >>
- No:22441
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
High inst MCCB for transformer primary side
It is a circuit breaker which has higher instantaneous tripping current value in order to prevent unwanted tripping by magnetizing inrush current of a transf... More Details >>
- No:22358
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Use in Particular Applications
-
ELCB Default setting Time-delay type sensitivity
Both of the adjustment knob is set to the maximum value when shipping in order to prevent unwanted earth leakage tripping when Earth Leakage Circuit Breaker ... More Details >>
- No:22388
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
AL/AX/SHT/UVT terminal markings and wire colors
The color of terminal identification tube and lead wire is same.For one AL switch, 98/ALa terminal : red, 96/ALb terminal : blue, 95/ALc terminal : grayFor S... More Details >>
- No:22396
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
Where UVT power supplied from?
Do not take the control power supply of UVT ("Resettable type" and "Reset prevention type") from the secondary side of the breakers. If taking the control po... More Details >>
- No:22415
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
Operating ambient temperature is set to - 10℃ to 40℃. ( However, its average over a period of 24h does not exceed 35℃.) In the case that the ambient temperat... More Details >>
- No:22370
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers