Time Delay type at the maximum operating time
The maximum operating time of Time-delay type Earth Leakage Circuit Breaker can be switched to 0.45s, 1.0s and 2.0s. The operating time is:* when it is 0.45s... More Details >>
- No:22375
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
Horizontal allowable distance when installing ACB
Flatness of mounting plane: 1 mm or less.In addition, it is necessary to consider the horizontality of the panel. More Details >>
- No:37698
- Release Date:2020/01/17 17:32
- Category: Air Circuit Breakers
-
Where UVT power supplied from?
Do not take the control power supply of UVT ("Resettable type" and "Reset prevention type") from the secondary side of the breakers. If taking the control po... More Details >>
- No:22415
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
It is the Earth Leakage Circuit Breaker with rated residual operating current of higher than 30mA but not exceeding 1000mA. We provide the products of "100, ... More Details >>
- No:22395
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
It is the Earth Leakage Circuit Breaker with rated residual operating current of 30mA or less. More Details >>
- No:22390
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
Operating ambient temperature is set to - 10℃ to 40℃. ( However, its average over a period of 24h does not exceed 35℃.) In the case that the ambient temperat... More Details >>
- No:22370
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
It is a button in order to mechanically trip a circuit breaker outside. It is used to confirm switching mechanism at the regular maintenance or sequence-chec... More Details >>
- No:22368
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
degrees of protection to IEC60529
The degess of protection for ACB is IP20 as standard (under the condition that front door is closed). For MCCB and ELCB, the degrees of protection can be IP2... More Details >>
- No:24812
- Release Date:2019/04/09 15:18
- Category: Molded Case Circuit Breakers
-
CP30-BA AL and AX switch micro-load can be provided. And the number of installation is same as standard AL and AX switch. However, if multiple AL and AX are ... More Details >>
- No:22427
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Equipment
-
It is possible to attach closely if there is no problem about the insulation distance between live parts such as a terminal bar and load currents are 80% or ... More Details >>
- No:22400
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers