FAQ


FAQAbout Products
- FAQ > Low-voltage Power Distribution Products > Low-voltage Circuit Breakers
FAQ
Keyword Search
FAQ within [ Low-voltage Circuit Breakers ]
-
It is same as the maximum rated operational voltage. More Details >>
- No:22365
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
How to connect to 2-pole breaker
(1) When "N" is marked on the breaker,connect the N phase wire as marked. (2) When "N" is not marked on the breaker, N phase wire can be connected to eith... More Details >>
- No:37700
- Release Date:2020/01/17 08:58
- Category: Molded Case Circuit Breakers
-
The number of trip durability by using SHT and UVT is 10% of the opening/closing number including the number of trips by overcurrent, trip button and test bu... More Details >>
- No:22407
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
It is the maximum voltage which meets the performance criteria for the rated operational voltage. More Details >>
- No:22367
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
B-ST is possible. More Details >>
- No:24814
- Release Date:2019/04/09 15:17
- Category: Molded Case Circuit Breakers
-
Earth Leakage Circuit Breaker and Earth Leakage Relay operate at higher than 50% but not exceeding 100% of the rated residual operating current IΔn. The eart... More Details >>
- No:22364
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
Insulating barrier in the package
Use the insulation barrier if they are packed with. If not using that, breaking performance is not guaranteed. For models that the insulation barrier is not ... More Details >>
- No:22406
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
Almost ELCBs can be connected n reverse. Check the item column of specification table "reverse connection (below 230 V AC)" in the catalog. If it says "Possi... More Details >>
- No:22434
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
This contact(SBC) is used to auxiliary switch(AXb) contact. When Drawout type ACB is moved from "test" position to "disconnect" position, AXb contact will b... More Details >>
- No:22416
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Type name of the operating handle
F-2SV is standard, F-2SVE is for emergency use. The difference is the color of the handle and its surroundings parts. More Details >>
- No:38028
- Release Date:2021/01/22 17:37
- Category: Accessories and Related Components
41-50 of Total 123