FAQ within [ Low-voltage Circuit Breakers ]
-
High inst MCCB for transformer primary side
It is a circuit breaker which has higher instantaneous tripping current value in order to prevent unwanted tripping by magnetizing inrush current of a transf... More Details >>
- No:22358
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Use in Particular Applications
-
Earth Leakage Circuit Breaker and Earth Leakage Relay operate at higher than 50% but not exceeding 100% of the rated residual operating current IΔn. The eart... More Details >>
- No:22364
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
It is a protection method which only trips the related circuit breaker and other fault-free circuit does not trip and continues power supply in the event of... More Details >>
- No:22366
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
AL/AX direct connection to PLC
It is necessary to use AL and AX switches that are suitable for the specification of PLC input unit. Generally AL and AX switch for micro-load are used for i... More Details >>
- No:22398
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
It is possible to reverse-connect if the circuit voltage of UL789 listed products is AC240V or less. Since they are double standard products of UL/CSA and CE... More Details >>
- No:22411
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
Storage temperature range of MCCBs and ELCBs
It is from -25 to 55℃ in Trip or OFF position. However, it shall be in an environment without condensation and freezing even in a short time. More Details >>
- No:22426
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
"b contact" is normally closed contact, and It is also called "NC (Normally Closed) contact". More Details >>
- No:22435
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
It is not possible to use standard AE-SW in DC circuit. Special DC use AE-SW is provided if specified. More Details >>
- No:22446
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Type name of the operating handle
F-2SV is standard, F-2SVE is for emergency use. The difference is the color of the handle and its surroundings parts. More Details >>
- No:38028
- Release Date:2021/01/22 17:37
- Category: Accessories and Related Components
-
It is same as the maximum rated operational voltage. More Details >>
- No:22365
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers