ACB How to check the operating characteristic
Y-2005 type field test equipment (it is sold separately) enable to check the operating characteristic easily. The test is conducted by connecting the test te... More Details >>
- No:22429
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Time Delay type at the maximum operating time
The maximum operating time of Time-delay type Earth Leakage Circuit Breaker can be switched to 0.45s, 1.0s and 2.0s. The operating time is:* when it is 0.45s... More Details >>
- No:22375
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
Earth leakage protective coordination
Since the total electric circuit length of upstream circuit breaker side is longer than that of downstream circuit breaker, constant earth leakage current b... More Details >>
- No:22369
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
We don't provide the earth leakage circuit beaker for PV power. Please use a general leakage circuit breaker. However, you need to select a reverse-connectab... More Details >>
- No:22348
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Use in Particular Applications
-
AL/AX direct connection to PLC
It is necessary to use AL and AX switches that are suitable for the specification of PLC input unit. Generally AL and AX switch for micro-load are used for i... More Details >>
- No:22398
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
It is voltage which ensures withstand voltage and it is used as basis to determine insulation distance. More Details >>
- No:22362
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Almost MCCBs can be connected n reverse. Check the item column of specification table "reverse connection" in the catalog. If it says "Possible", MCCB can be... More Details >>
- No:22442
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
When Power-Fuse (PF) is used as a high-voltage side protection device, coordination with MCCBs on the secondary side shall be achieved. Therefore, MCCB has l... More Details >>
- No:22403
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Use in Particular Applications
-
Inverse time delay operating characteristic
It is a characteristic that operating time inversely become shorter as current increases. For Molded Case Circuit Breakers, protection characteristic meeting... More Details >>
- No:22387
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
ELCB applicable to harmonics and surge
Compared with general circuit breakers, Earth Leakage Circuit Breaker applicable to harmonics and surge has earth leakage current detecting characteristic wh... More Details >>
- No:22344
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers