- FAQ > Low-voltage Power Distribution Products > Low-voltage Circuit Breakers
FAQ
Keyword Search
FAQ within [ Low-voltage Circuit Breakers ]
-
The number of trip durability by using SHT and UVT is 10% of the opening/closing number including the number of trips by overcurrent, trip button and test bu... More Details >>
- No:22407
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
Change Electronic relay characteristics when it is energized
Only electricians who have enough technical knowledge should change the setting of overcurrent tripping and earth leakage tripping characteristics. Moreover,... More Details >>
- No:22409
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
The circuit breaker is designed to attain a predetermined value of limiting non-actuating time corresponding to a given value of residual current. Our time-d... More Details >>
- No:22351
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
It is voltage which ensures withstand voltage and it is used as basis to determine insulation distance. More Details >>
- No:22362
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Ground fault protection (GFR) is prepared as option, it is possible to detect and protect against ground fault current. "Trip" or "Alarm signal output" can b... More Details >>
- No:22412
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
It is a button in order to trip MCCB. It is used for regular inspection of the switching mechanism, and trip condition of MCCB when Alarm switch (AL) and Shu... More Details >>
- No:22444
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Bar terminal material for 400A is aluminum alloy, and for 630A or higher is copper. More Details >>
- No:24819
- Release Date:2019/04/09 15:13
- Category: Molded Case Circuit Breakers
-
It is not possible to use standard AE-SW in DC circuit. Special DC use AE-SW is provided if specified. More Details >>
- No:22446
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
No, you must not use 2-pole circuit breaker as 1-pole circuit breaker (series connection as only single phase ). If using it as 1-pole circuit breaker, these... More Details >>
- No:22382
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Where UVT power supplied from?
Do not take the control power supply of UVT ("Resettable type" and "Reset prevention type") from the secondary side of the breakers. If taking the control po... More Details >>
- No:22415
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components